London
London - Level 3 Data Center
Building Overview
Modern Data Center located in eastern London is opened in 1999 and technical equipment takes up five floors, i.e. over 8000 m2.
London Data Center is connected to the following providers - Level 3, Colt, BT, C&W, WorldCom, Neos, Viatel, Fibrenet, 51 degrees.
Technical Specification
Main power source
Power source - Dual redundant 4MVA, 11kV dedicated underground cable feeds to dedicated dual redundant 4MVA transformer substation.
Generators
In case of emergency there are two diesel generators which give 4.4 MV power, with automatic start and reaching full power in less than one minute. Tank can store enough fuel for 24 hour continuous operations.
UPS
With under-floor power track distribution system and dual redundant AELB distribution strategy, each UPS module provides 15-minute battery autonomy.
DC
Universal distribution system with dual redundant, with four hours of battery autonomy and power system of 800 amp -48VDC.
Conditions
Fully regulated humidity and temperature, with option of cooling capability over the gross space, where technical areas are positively pressurized to minimize dust ingress.
Fire Protection
Very Intelligent Early Warning (VIEW) detection system and smoke extract system activated by fire alarm represent the top quality of fire protection measures. Where it was possible, non-inflammable and low-smoke zero halogen materials were used, while flammable materials are not stored anywhere near technical equipment. The building is split into sealed, independent, fire compartments.
London 1 Gateway
Security
Building is remotely monitored 24/7/365 and it has full electronic access control system, based on proximity cards with photo and PIN keypads.
Closed Circuit Television (CCTV)
Video monitoring and recording of all access points and circulation areas.
Building Monitoring System (BMS)
Building is monitored 24/7/365 through Control center for monitoring operations and local monitoring creates logs of temperature and humidity conditions and alarms. There is also full perimeter under-floor leak detection linked to building monitoring system.
Infrastructure
Facility is designed to accommodate standard rack/cabinets of 220 cm nominal height. All electric installations are under floor, and fiber and copper cabling are distributed overhead. Fiber entry to the building is via two independent points.
Gallery
Become our Facebook fan and get an extra discount!
facebook.com/eunethostingSharepoint 2010 servis
Delite i arhivirajte dokumenta, učestvujte u diskusijama i anketama sa kolegama, a sve to u poznatom i sigurnom okruženju bez brige o održavanju, licencama i backupu.
Exchange hosting servis
Možete pristupiti vašem email-u, ličnim i grupnim kalendarima, zajedničkim folderima i planovima bilo kada i bilo gde!Omogućen je pristup putem mobilnog telefona: Smartphone, Blackberry...
Cloud Mail Server
Ovaj servis omogućava vama i vašim zaposlenima da na najsigurniji način pristupate email-u, kako unutar kompanije, tako i sa bilo koje lokacije na svetu na kojoj postoji Internet konekcija.
Audio streming
AudioStreaming vam omogućava da pokrenete sopstvenu radio stanicu. Obezbedite da se vaš signal čuje svuda u svetu, bez obzira na lokaciju.